2000-2500 AMPERE P FRAMES CLASS 675,676 | ||||
Square D Parts | SQUARE D BREAKERS | 100 AMP FRAME | 100, 225, and 250 amp Frame | 400,600, 1000, 1200 AMP FRAME |
Square D 2000-2500 Amp P Frames Class 675,676
Thermal Magnetic Molded Case Circuit Breakers
Square D Circuit Breakers are stocked extensively and offered along with switches, motor circuit protectors, quality service, fair pricing, and fast turnaround on repairs and replacements. Molded Case Circuit Breaker test results are available upon request. We Specialize in the obsolete, hard to find, older style circuit breakers as well as current style frames from SQUARE D
Click here for Square D P Frame Rating Column Kits at our online store
2000 AMPERE rating PAF |
AC MAGNETIC TRIP SETTINGS AMPERES
|
2 POLE--600 Vac | 3 POLE--600 Vac | |||
FRAME ONLY | RATING COLUMNS TWO PER KIT | FRAME ONLY | RATING COLUMNS THREE PER KIT | |||
LOW | HIGH | CATALOG No. | KIT CATALOG No. | CATALOG No. | KIT CATALOG No. | |
600 | 3200 | 9000 | PAF2026 | PA2600RC | PAF2036 | PA3600RC |
700 | 3200 | 9000 | PA2700RC | PA3700RC | ||
900 | 3200 | 9000 | PA2800RC | PA2800RC | ||
1000 | 3500 | 9000 | PA21000RC | PA31000RC | ||
1200 | 3500 | 9000 | PA21200RC | PA31200RC | ||
1400 | 4500 | 9000 | PA21400RC | PA31400RC | ||
1600 | 5000 | 10000 | PA21600RC | PA31600RC | ||
1800 | 6500 | 11000 | PA21800RC | PA31800RC | ||
2000 | 8000 | 12000 | PA22000RC | PA32000RC | ||
HIGH INTERRUPTING: COMPLETE CIRCUIT BREAKER REQUIRES FRAME AND RATINGS
COLUMNS
Click here for Square D P Frame Rating Column Kits at our online store
2000 AMPERE rating PHF |
AC MAGNETIC TRIP SETTINGS AMPERES
|
2 POLE--600 Vac | 3 POLE--600 Vac | |||
FRAME ONLY | RATING COLUMNS TWO PER KIT | FRAME ONLY | RATING COLUMNS THREE PER KIT | |||
LOW | HIGH | CATALOG No. | KIT CATALOG No. | CATALOG No. | KIT CATALOG No. |
600 | 3200 | 9000 | PHF2026 | PA2600RC | PHF2036 | PA3600RC |
700 | 3200 | 9000 | PA2700RC | PA3700RC | ||
900 | 3200 | 9000 | PA2800RC | PA2800RC | ||
1000 | 3500 | 9000 | PA21000RC | PA31000RC | ||
1200 | 3500 | 9000 | PA21200RC | PA31200RC | ||
1400 | 4500 | 9000 | PA21400RC | PA31400RC | ||
1600 | 5000 | 10000 | PA21600RC | PA31600RC | ||
1800 | 6500 | 11000 | PA21800RC | PA31800RC | ||
2000 | 8000 | 12000 | PA22000RC | PA32000RC | ||
HIGH INTERRUPTING:
COMPLETE BREAKER REQUIRES FRAME AND RATINGS COLUMNS
Click here for Square D P Frame Rating Column Kits at our online store
2500 AMPERE rating PCF |
AC MAGNETIC TRIP SETTINGS AMPERES
|
2 POLE--600 Vac | 3 POLE--600 Vac | |||
FRAME ONLY | RATING COLUMNS TWO PER KIT | FRAME ONLY | RATING COLUMNS THREE PER KIT | |||
LOW | HIGH | CATALOG No. | KIT CATALOG No. | CATALOG No. | KIT CATALOG No. |
1600 | 6000 | 12000 | PCF2526 | PC21600RC | PCF2536 | PC31600RC |
1800 | 6000 | 12000 | PC21800RC | PC31800RC | ||
2000 | 6000 | 12000 | PC22000RC | PC32000RC | ||
2500 | 8000 | 14000 | PC22500RC | PC32500RC |
INTERRUPTING RATINGS (kA)
PAF | PHF | PCF | |
240v | 65 | 125 | 125 |
480v | 50 | 100 | 100 |
600v | 42 | 65 | 65 |
PAF and PHF circuit breakers can be bus or cable connected. For cable connections, optional terminal pad kit PALTB or equivalent bus structure is required. PALTB kit contains terminal pads for one end of the circuit breaker only and has provisions for mounting a maximum of six lugs per phase.
PCF circuit breakers Require terminal pads for both ends of the circuit breaker. Terminal pads have provisions for mounting a maximum of eight lugs per phase.
[Visit our e-commerce site: www.SouthlandElectrical.com]